Archive for the ‘14 Villa – Rumaihi’ Category
Approved form – 14 Villa_Rumaihi
August 26, 200814villa_rumaihi_17aug2008
August 20, 2008
Compliance List for 17august2008 CDD/Edwin Mejia’s comments
14 VILLA COMPOUND for MR. SA’AD MOH’D SA’AD AL RUMAIHI
Item |
Comment |
Compliance |
|
Floor Plan |
|
1. |
The minimum tread depth of new stair is 11 inches (280mm). Please check and revise the stair’s tread depth. |
Complied. |
2. |
Please provide occupant load and exit width capacity calculations of clubhouse to demonstrate the adequacy of means of egress / ingress in accordance with NFPA 101. |
Complied. See sheet no. F-C-201 for occupant load and exit width calculations for Clubhouse.
|
3. |
Please change the swing direction of double panel doors at clubhouse into exit direction. Please check and revise.
|
Complied. |
4. |
Hazardous area shall be separated from other parts of the building by fire barriers having a fire resistance rating of not less than 1 hour or shall be protected by automatic extinguishing systems.
In this connection, please enclose kitchen area at clubhouse with at least 1-hour fire resistance rating with self-closing fire rated door. Please check and revise.
|
Complied. We enclose the kitchen with 1-hour fire resistance rating with self-closing 20 minutes fire rated door. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|