Archive for the ‘14 Villa – Rumaihi’ Category

Approved form – 14 Villa_Rumaihi

August 26, 2008

14villa_rumaihi_17aug2008

August 20, 2008

 

 

 

 

 

Compliance List for 17august2008 CDD/Edwin Mejia’s comments

14 VILLA COMPOUND for MR. SA’AD MOH’D SA’AD AL RUMAIHI

 

 

Item

Comment

Compliance

 

Floor Plan

 

1.

The minimum tread depth of new stair is 11 inches (280mm). Please check and revise the stair’s tread depth.

Complied.

2.

Please provide occupant load and exit width capacity calculations of clubhouse to demonstrate the adequacy of means of egress / ingress in accordance with NFPA 101.

Complied. See sheet no.

F-C-201 for occupant load and exit width calculations for Clubhouse.

 

3.

Please change the swing direction of double panel doors at clubhouse into exit direction. Please check and revise.

 

Complied.

4.

Hazardous area shall be separated from other parts of the building by fire barriers having a fire resistance rating of not less than 1 hour or shall be protected by automatic extinguishing systems.

 

In this connection, please enclose kitchen area at clubhouse with at least 1-hour fire resistance rating with self-closing fire rated door. Please check and revise.

 

Complied. We enclose the kitchen with 1-hour fire resistance rating with self-closing 20 minutes fire rated door.